In this video
- Sight glasses installed at the low points of a coiled line set reveal exactly how much oil and refrigerant settle out when the unit is running and when it's off.
- Oil does foam and briefly pool at low points after shutdown, but the total amount recovered is tiny.
- Out of six full coiled loops, all the oil that settled out measured roughly one ounce, compared with about 10 ounces of oil in the whole system.
- The compressor only needs 2 to 3 ounces of oil to run, so the extra oil is a built-in buffer for long line runs and future top-offs.
- Coiled vertical line sets only become a real concern with very long runs and an outdoor unit mounted higher than the indoor unit, such as a rooftop condenser.
Questions this video answers
Does coiling or looping a mini split line set trap oil and damage the compressor?
A small amount of oil does settle at the low points of a coiled line set when the unit is off, but Airspool's sight-glass test showed it amounts to roughly one ounce out of six full loops, far too little to cause a problem in a typical installation.
How much oil is normally inside a mini split refrigerant system?
On the 12,000 BTU R-32 system tested, the compressor holds about 10 ounces of oil even though it only needs 2 to 3 ounces to actually run. The extra oil is there to compensate for long line runs and future oil top-offs.
What's the difference between refrigerant migration and oil trapping in a line set?
Refrigerant migration is liquid refrigerant settling in the lines, while oil trapping is the lubricating oil settling out separately. The sight glass shows mostly refrigerant with only a small fraction of it actually being oil.
When should I actually worry about oil return in a mini split line set?
Oil return becomes a real concern only with very long vertical line runs where the outdoor unit sits higher than the indoor unit, such as a rooftop condenser feeding a lower indoor head, not in a typical setup where the outdoor unit is at or below the indoor unit.
What is the accumulator for in a mini split outdoor unit?
The accumulator traps any liquid refrigerant that hasn't fully evaporated before it can reach the compressor, since liquid refrigerant passing through the compressor can damage it.
Does the amount of trapped oil change between cooling mode and heating mode?
Yes. In the test, less oil and liquid settled out after the unit ran overnight in heating mode compared with cooling mode, and the suction line showed almost none.
Why does refrigerant boil in the line set even with no heat applied?
Refrigerant is a volatile gas that boils at or below room temperature, so once the system shuts off and pressure drops, it boils off on its own without any outside heat source.
Transcript
Read the full transcript
Hey guys, Dave and Todd here. There's been a great debate between both amateurs and professionals about what happens when you vertically coil refrigerant lines behind a mini split. Does that trap the oil, pulling it into the line so that when the unit starts up there isn't enough oil, or even while the unit's running, the oil gets trapped there and that becomes an issue? So we put sight glasses into the line set at the lowest points to see what actually happens.
Todd already knows what's going to happen, because we did this same test last night. We're assuming it'll turn out the same way, but let's find out. So, turn the unit on. Okay, it's on, and there goes the refrigerant. See that foaming? That's actually the oil foaming, on the low-pressure line.
It's hard to tell direction, but this is the liquid line, so you'll see liquid coming through here. Again, that foam is the oil, and the liquid is moving toward our expansion device, also known as our indoor unit.
You can still see a little bit of liquid, is that oil, or liquid and oil mixed? In the suction line there's still a little liquid, but most of the liquid has evaporated in the indoor unit and become a gas. That's why the outdoor unit has what's called an accumulator, which traps any liquid refrigerant before it reaches the compressor. You can see very little liquid here, and some of that's oil, but if any liquid does come back to the outdoor unit, the accumulator catches it, because you can't let liquid refrigerant go through the compressor.
This is how things look right now, and it'll stay this way as long as the unit is running. The high-pressure liquid refrigerant, mostly or all liquid, is going this way, and going the other way is the gas, with a little bit of liquid and oil mixed in.
Now we're going to turn it off, go ahead, Todd, and see what happens. I'll stay on the sight glasses here. It'll take a little while for the liquid to boil off on that side. There, the liquid is boiling off and foaming up, kind of like a car windshield fogging in cold weather. That's because the expansion device is already in the outdoor unit, but there's further expansion happening in the indoor unit.
Okay, it's settling down here. This is the high-pressure line, the one going to the indoor unit, and there's a little bit of oil in there, just a tiny bit. In the suction line, the one going to the compressor, it's hard to tell, but this is a fairly deep well, and there's enough to coat the bottom. There's a little more oil in the high-pressure line because more refrigerant runs through there and there's more pressure, so it makes sense that when things settle down, there's more oil on that side.
So how much oil is this? We took these two low points, the settlement points, and Todd replicated the test with six line loops instead of the four coils we have here. In total, this system has 10 ounces of oil in the compressor, but the compressor only needs 2 or 3 ounces to actually run. So it's overfilled with oil on purpose: if you ever need to add oil down the road, or if you have super long refrigerant line runs, that extra oil helps compensate. So you can't say, mythbusters-style, that there's no oil in a coiled loop, there is oil in here. But out of six full loops, all of the oil that settled out fits into what looks like maybe an ounce from a 16.9-ounce bottle. So yes, there's oil in this loop, but it's minuscule compared to what's sitting in the compressor.
The compressor has a sump built to maintain its oil supply, but you do want some oil traveling through the system, because things need to be lubricated, the reversing valve, the expansion valve, and any other moving part in the refrigerant system. So oil circulating through the system is a good thing.
A little bit does get trapped in a coiled loop. If your outdoor unit is on the roof with a really long line set and you're running several coils, you could be asking for trouble. But in a normal setup, where your outdoor unit sits below your indoor unit, you'll be fine, even the small amount of oil that gets trapped won't affect performance at all.
That's Todd's conclusion, backed by decades in the business, he's been doing this a long time. Now we're going to pause the test one more time. Keep in mind, everything so far was with the unit running in cooling mode, you might be asking, what happens in heating mode? So we'll pause again and show you.
Now the unit is running in heating mode. The flow direction has reversed, it's hard to tell by eye, but the liquid line is now feeding back toward the outdoor unit, which becomes the expansion device. Everything is just reversed: the same lines are still high-pressure and low-pressure, but the roles have flipped.
There's liquid in this one. Now, turn it off, Todd. Again, some of the refrigerant needs to boil off before things settle down, we let it sit overnight, and there was even less oil this time. That matters because if you're starting your unit up again after just a few hours, you're hoping there's less liquid sitting at the low points of the lines. There is a little oil here, but not much, and in the suction line I'm not really seeing any after running in heating mode.
So that's the conclusion: both sides of the debate are right. Oil does get trapped in a coiled or looped line set. But the manufacturers design around it, because they know it's a potential issue, that's exactly why they put more oil in the system than is strictly necessary.
Anything else to add, Todd? You're probably wondering why the refrigerant was boiling with no heat applied to it, that's because refrigerant is a volatile gas, meaning it boils at or below room temperature. So it'll boil off all by itself, just sitting in the room.
Hopefully you got something out of this, if so, give it a thumbs up. We talk about air conditioning, solar power, and solar air conditioning here on our channel, which is appropriately enough called Airspool, because that's the name of our company. Subscribe if you're interested, drop a comment, hit thumbs up, and thanks a lot for your time.