In this video
- Explains why you'd pump down a system: to safely relocate the outdoor unit while storing refrigerant back inside it, just like it shipped from the factory.
- Shows how multi-zone systems differ from single-zone: as long as the running zones are calling for cooling, their valves stay open and the unit pumps down the same way.
- Demonstrates closing the liquid lines first, watching pressure drop to zero, then closing the suction lines and shutting off the units.
- Explains that inactive zones are inherently closed, so there's nothing extra to do for zones that aren't running.
- Highlights Airspool's twist-to-connect valves, which make disconnecting and relocating a solar hybrid multi-split especially simple.
Questions this video answers
Can I pump down a multi-split mini-split system the same way as a single-zone unit?
Yes. As long as the zones you have connected are running and calling for cooling, their valves stay open and you can pump the refrigerant back into the outdoor unit the same way you would on a single-zone system: close the liquid lines, let the pressure drop to zero, then close the suction lines.
Why would I need to pump down a mini-split system?
Pumping down stores the refrigerant back inside the outdoor unit, just like it shipped from the factory, so you can safely move the unit. Once it's relocated, you pressure test, evacuate, and release the refrigerant again.
Do I need to close all the zone valves on a multi-zone system, or just the ones running?
You only need to worry about the zones that are actively running and calling for cooling, since their solenoid valves are open. Zones that aren't running are already closed, so there's nothing extra to do for them.
What order do I close the valves in when pumping down a multi-split system?
Close the liquid lines first, then watch the pressure drop toward zero. As it gets close, start closing the suction lines gradually so you don't have to turn the valve stem too far in one go, then shut off the indoor and outdoor units.
Can I use one gauge instead of gauges on every zone when pumping down a multi-split?
Yes. Because the suction sides of all the zones are tied together, the pressure stays roughly the same across zones, so a single gauge on one port gives you an accurate reading even without a multi-port manifold.
Will I pull air into the line set if there's a leak while pumping down?
No. A leak just means you lose refrigerant, it doesn't pull air in, because you'd need a vacuum (negative pressure) in the lines to draw anything in, and closing the valves once you hit zero pressure doesn't create that vacuum.
How long can I run the compressor during a pump-down?
Don't run it any longer than necessary to get the pressure down to zero. Leaving it running after that starts straining the compressor.
Do I need to tighten the service valve caps after pumping down a system?
Yes, snug them back down after you finish, though you don't need heavy torque like 100 foot-pounds. Without the caps in place, the service valves can leak refrigerant over time.
Transcript
Read the full transcript
Hi guys. Two years later, we have Todd here, back in front of the camera. A couple of years ago, we made a video that talked about how to pump down a mini-split to get the refrigerant back into the outdoor unit. Some of you have multi-split units and wanted to know how to do this on a multi-split system, so Todd will go over that.
So, Todd, first of all, why would you want to do this? Well, in case you need to move the outdoor unit, you need to store the refrigerant back into the outdoor unit like it came from the factory. Then you can move it and go through your process of pressure testing and evacuating before eventually releasing the refrigerant again.
But the fear of pumping down a multi-split system is really not as difficult as you'd think. As you can see right here, this one has up to three zones. As long as whatever zones are hooked up are calling for cooling, the valves are open, and you can do the exact same thing you did on a single system: close the liquid lines, wait for it to pump down to zero, close the suction lines, and turn it off.
So all the zones are tight and cooling when you begin? That's right. There are solenoid valves that open when the zones are running and cooling — on the discharge side and the suction side, they're all tied together. So I put two gauges on here so you can see the two zones, and you'll see when I close the valves, the pressures will stay pretty much the same all the way down.
We'll take a look at that. These are the two units we're going to be pumping down — you can see they're both set to cooling, at 63 degrees and 66 degrees. So yes, make sure they're in cooling before you do this.
All right, liquid line — you're closing... it doesn't matter which one you close first, right, because you're closing B before A? Well, yeah, it doesn't matter. You're going to close the liquid lines, and then these are your suction lines that you'll close once it pumps down to zero. You see it dropping — this is a two-ton unit, so it's going to take a little bit longer than the one-ton units. As it gets closer to zero, start closing the valves. That way you don't have to turn so far.
See how they're staying pretty much the same pressure? Yeah. So if you had a leak in one of these lines, would you be pulling air in right now? No, you wouldn't. Well, first of all, if you had a leak, you wouldn't have any refrigerant. But you'd have to put a negative pressure on these line sets to pull anything into them — once they're at zero, there's no way to pull anything in. It takes a vacuum to pull anything in.
All right, we're getting down below 50. So what I do is start closing the valves a little bit as I get close, that way I don't have to turn so far, and I have a way of shutting the unit off as you get real close. In other words, you really only need a hose or gauge hooked up on this one port right here, because you can see they're pretty much the same.
Right. So if you don't have one of these fancy field-piece gauges, your normal gauge will work off of just one line, because they're pretty much the same. Okay, and this works for a system with three, five, or however many zones, as long as they're all in cooling? Right. And if you have a zone that isn't running, that's not an issue either, because that valve is just closed. Inherently closed.
So we're down at five... zero... zero. And now we're going to turn off the units. You don't want to let this run too long, because that will start straining the compressor. So now both of the units have been turned off, and you'll see there's a little bit of residual pressure that comes up — a little bit of refrigerant left in there, but not enough to worry about. Okay, all closed, just like it came from the factory.
Wonderful. So now you can move the unit, and you can release the refrigerant later. And when you move it and reinstall it, you can pull a vacuum on these lines again, right? Yeah, absolutely — that's what you should do. One more point here: these service valve caps, you really should tighten them, but not to something crazy like 100 foot-pounds of torque — just snug, after you're done, because they will leak if you don't have those caps on.
Okay. And if you have any questions or comments, put them in the comments after this video. Give us a thumbs up if this helped.
By the way, at Airspool we do solar-powered hybrid multi-splits, so you'll see — if you ever did want to move the unit, these valves right here are twist-to-connect. So right now we could disconnect these valves and move this unit anywhere we wanted. You can also take the indoor units and move them to any other room you want, and then you'd be back in action. So it's very simple with the Airspool unit.
Subscribe to the Airspool channel if you want to talk about air conditioning, solar, or solar-powered air conditioning. Thanks for your time. Bye-bye.